Mã lỗi máy lạnh Haier

Trung tâm bảo hành máy lạnh Haier xin gởi đến quý khách bảng mã lỗi của máy lạnh Haier, nếu quý khách đang dùng máy lạnh mang thương hiệu Haier nhưng gặp một trong các lỗi trên xin trực tiếp gọi đến trung tâm Haier của Gia Khang để được bảo hành sớm nhất. 

Bảng mã lỗi máy lạnh Haier:

E01 flow switch fault

Troubleshooting:stop all module chillers

Faliure resume:this fault is unresume failure

Must cut off power,after eliminate failures,then restart

E05 triple-phase AC input lack phase protection

Troubleshooting:stop all compressors、water pump、fan motor(if master unit occurs this

fault,all modules will stop,slave unit occurs this fault, only corresponding module unit will stop);

Troubleshooting resume:after AC input is normal,will auto resume;

E06 triple-phase AC input phase sequence protection

Troubleshooting:stop all compressors、water pump、 fan motor(if master unit occurs this

fault,all module units will stop,if slave unit occurs this fault,only corresponding module unit will

stop );

Failure resume:after power off,adjust phase sequence,will resume.

E07 water return sensor fault

Troubleshooting:stop all compressors、water pump(if master unit occurs this fault,all

module units will stop,if slave unit occurs this fault,unit won’t do stop protection);

Faliure resume:resume after change ambient sensor normally;

E08 water outlet temp. sensor fault

Troubleshooting:stop this unit’s all compressors;

Faliure resume:resume after change temp. sensor normally.

E09 outdoor ambient temp. sensor fault

Troubleshooting: stop this unit’s all compressors;

Faliure resume:resume after change temp. sensor normally;

E16 wired controller communication fault

Troubleshooting:system will do “OFF”manage

Faliure resume:auto resume after receiving wired controller communication signals.

E21 fan overload protection fault

Troubleshooting:stop this unit’s compressor

Faliure resume:unresumable

E22 A system high pressure protection

Troubleshooting:A system compressor stop;

Faliure resume:resume after signals shut;

E23 A system low pressure protection

Troubleshooting:A system compressor stops;

Failure resume: resume after signals shut;

E24 compressor 1 over current protection

Troubleshooting:A system compressor stops;

Faliure resume:auto resume;

E25 compressor 1 discharge temp. sensor open circuit or short circuit

Troubleshooting:A system compressor stops;

Failure resume:auto resume after changing sensor normally;

E26 A system coil(outlet) temp.sensor is open circuit or short circuit

Troubleshooting:stop A system compressor

Failure resume:auto resume after changing sensor.

E28 A system water exchange refigerant entrance port is open circuit or short circuit

Troubleshooting:stop A system compressor;

Failure resume:auto resume after changing sensor normally;

E29 A system suction temp. sensor is open circuit or short circuit

Troubleshooting:stop A system compressor

Failure resume:auto resume after changing sensor normally;

E30 A system coil(entrance)temp. sensor is open circuit or short circuit

Troubleshooting:A system compressor stops;

Failure resume:auto resume after changing sensor normally.

E31 compressor 1 discharge temp. sensor overhigh

Troubleshooting:A system compressor stops;

Failure resume:resume after changing temp. sensor or discharging temp. sensor<90℃

E32 A system coil (exit) temp.sensor temp. overhigh

Trooubleshooting:A system compressor stops;

Failure resume:resume after A system coil(exit) senor temp.<55℃

E39 compressor 2 overcurrent protection

Troubleshooting:A system compressor stops;

Failure resume: auto resume;

E40 compressor 2 discharge temp. sensor is open circuit or short circuit

Troubleshooting:A system compressor stops;

Failure resume:auto resume after change sensor normally;

E46 compressor 2 discharge temp. is overhigh

Troubleshooting:A system compressor stops;

resume:resume after compressor 2 discharge temp.<90℃

E52 B system high pressure protection

Troubleshooting:B system compressor stops;

Failure resume:auto resume after signals shut

E53 B system low pressure protection

Troubleshooting:B system compressor stops;

Failure resume:auto resume after signals shut;

E54 compressor 3 over current protection

Troubleshooting:B system compressor stops;

resume:auto resume.

E55 compressor 3 discharge temp. sensor is open circuit or short circuit;

Troubleshooting:Bsystem compressor stops;

Failure resume:auto resume;

E56 B system coil(exit) temp. sensor is short circuit or short circuit

Troubleshooting:B system compressor stops;

Failure resume:auto resume after changing sensor normally.

E57 B system water exchange refirgerant entrance temp.sensor is open circuit or short

circuit

Troubleshooting:B system compressor stops;

Failure resume:auto resume after changing sensor normally;

E58 B system water exchange refrigerant exit temp. sensor is open circuit or short circuit

Troubleshooting:B system compressor stops;

Failure resume: auto resume after changing sensor normally.

E59 B system suction temp. sensor is open circuit or short circuit

Troubleshooting:B system compressor stops;

Failure resume:auto resume after changing sensor normally

E60 B system coil(entrance) temp. sensor is open circuit or short circuit

Troubleshooting:B system compressor stops;

Failure resume:auto resume after changing sensor normally;

E61 compressor 3 discharging temp. sensor overhigh

Troubleshooting:B system compressor stops;

Failure resume:resume after changing temp. sensor or discharging temp. overhigh;

E62 B system coil(exit) temp. sensor overhigh

Troubleshooting:B system compressor stops;

Failure resume:resume after B system coil(exit) sensor temp<55℃

E69 compressor 4 overcurrent protection

Troubleshooting:B system compressor stops;

Failure resume:auto resume;

E70 compressor 4 discharging temp. sensor is open circuit or short circuit

Troubleshooting:B system compressor stops;

Failure resume:auto resume after changing sensor normally;

E76 compressor 4 discharging temp. sensor is overhigh

Troubleshooting:B system compressor stops;

Failure resume:resume after changing temp. sensor or discharging temp. <90℃

 

MỌI CHI TIẾT XIN LIÊN HỆ :

 

 

Hotline : 0978 89 0978

 

TRUNG TÂM ĐIỆN LẠNH GIA KHANG

 

 

VPĐD : Số 52, Đường D2, P.25 - Quận Bình Thạnh, TP.HCM

Trụ sở chính: Đường số 42, P. Tân Quý, Quận 7, TP.HCM

Trụ sở 1: 19A, Đường Quang Trung, Quận Gò Vấp, TP.HCM

Trụ sở 2: Số 143, Đường Ngô Quyền, Quận 5, TP.HCM

Trụ sở 3: 54, Đường Điện Biên Phủ, Phường 1, Quận 3, TP.HCM

Trụ sở 4: Số 143, Đường Lê Trọng Tấn, Quận Tân Phú, TP.HCM

Tổng đài: 0866 841 145 - Hotline : 0978 89 0978

Website: http://dienlanhgiakhang.com

Email: This email address is being protected from spambots. You need JavaScript enabled to view it.